Skip to content
OSWAL CABLESCables · Conductors · EPC

Aluminum XHHW-2 / RW90

Compact AA-8000 series aluminium alloy conductor with cross-linked polyethylene insulation for service, feeder and branch circuits in wet or dry locations up to 90°C.

  • Aluminum XHHW-2 / RW90
  • Aluminum XHHW-2 / RW90

Applications

Where it is used

  • Service, feeder and branch circuits in conduit or raceway
  • Wet and dry locations up to 90°C
  • Cable tray rating for 1/0 AWG and above on request
  • Sunlight exposed installations

Construction

What it's built from

Conductor
Compact bare AA-8000 aluminium alloy, Class B
Insulation
Cross-linked polyethylene (XLP), ten solid colours
Temperature rating
90°C wet or dry
Surface
Low coefficient of friction 'slick' finish

Technical specifications

Sizes & ratings

Selected sizes — nominal values

Size AWG/kcmilCond. dia. (in)Insulation (in)OD (in)Weight (lbs/kft)Ampacity 75°C (A)Ampacity 90°C (A)
80.1340.0450.227304045
60.1690.0450.262425055
40.2130.0450.306586575
20.2680.0450.3618690100
1/00.3360.0550.449134120135
4/00.4750.0550.588247180205
3500.6160.0650.749401250280
5000.7360.0650.869556310350
7500.9080.0801.071833385435
10001.0600.0801.2231,090445500

Ampacities for not more than three conductors in raceway, cable or earth at 30°C ambient per Table 310.16 of the 2020 NEC. Full size range in the datasheet.

Standards

Referenced specifications

  • UL 44 / CSA C22.2 No. 38
  • UL 1685
  • ANSI/NEMA WC-70 / ICEA S-95-658
  • ASTM B800, B801
  • Federal Spec A-A-59544A
  • NFPA 70 NEC
  • CSA C22.1 CEC