Skip to content
OSWAL CABLESCables · Conductors · EPC

ACSS/TW

Used as bare overhead transmission cable and as primary and secondary distribution cable. It is designed to continuously operate up to 250°C without losing strength.

  • ACSS/TW

Construction

What it's built from

Construction
Aluminum alloy 1350 wires, concentrically stranded around a steel core with one or more layers of 63% minimum average conductivity aluminum 1350-O wire stranded around it.
Mechanical load
The steel core carries most or the entire mechanical load of the conductor due to the fully annealed or soft temper aluminum.
Core protection
The steel core wires are protected from corrosion by a zinc-5% aluminum-mischmetal-alloy coating.
Sizing
Diameter or Area Equal to Standard ACSR Sizes.

Technical specifications

Sizes & ratings

ACSS/TW – ASTM B-857

Code wordSize (kcmil)Type no.Alu area (sq. in)Total area (sq. in)Layers of AluAlu wiresSteel wiresSteel core dia.Complete cable dia.Alu weight (lbs/kft)Steel weight (lbs/kft)Total weight (lbs/kft)Standard strength (lbs)High strength (lbs)Ultra high strength (lbs)
Flicker ACSS/TW477130.37470.42332187 x 0.09400.2820.77644816561213,00014,20016,400
Hawk ACSS/TW477160.37460.43562187 x 0.10530.3160.79044820665515,60017,10019,800
Dove ACSS/TW556.5160.43710.50832207 x 0.11380.3410.85052324176518,20019,90023,100
Mystic ACSS/TW666.6130.52360.59152207 x 0.11110.3330.91062623085618,20019,90022,900
Maumee ACSS/TW768.2130.60410.68262207 x 0.11950.3580.98072126698721,00023,00026,500
Wabash ACSS/TW762.8160.59920.69662207 x 0.13310.3990.990717330104724,90026,90031,200
Drake ACSS/TW795160.62440.72612207 x 0.13600.4081.010748344109225,90028,00032,500
Rail ACSS/TW954.070.74930.80113327 x 0.09710.2911.060899176107516,70018,00020,400
Cardinal ACSS/TW954.0130.74930.84642207 x 0.13290.3991.084896329122526,00028,00032,300
Suwannee ACSS/TW959.6160.75370.87622227 x 0.14930.4481.108903415131830,70033,10038,600
Curlew ACSS/TW1033.5130.81170.91692217 x 0.13830.4151.130970356132628,20030,30035,000
Hudson ACSS/TW1158.4130.90921.02802257 x 0.14670.4401.1961087401148831,10033,50038,800
Grackle ACSS/TW1192.5130.93661.055433819 x 0.08920.4461.2251126403152932,60035,50041,500
Pheasant ACSS/TW1272.0130.99901.125033919 x 0.09210.4611.2601201429163034,10037,30043,000
Martin ACSS/TW1351.5131.06201.196433919 x 0.09490.4701.3001276456173236,20039,60045,600
Merrimack ACSS/TW1433.6131.12501.267733919 x 0.09780.4891.3401356484184038,40042,00048,400
Pecos ACSS/TW1622.0131.27361.442533919 x 0.10640.5321.4201531573210445,00049,30056,900
Chukar ACSS/TW1780.081.39861.512633719 x 0.08740.4371.4501673388206135,30038,20043,900
Cumberland ACSS/TW1926.9131.51341.704934219 x 0.11330.5671.5451819650246951,60056,40065,000
Santee ACSS/TW2627.382.06302.231746419 x 0.10620.5311.7612492571306351,30055,60063,100

All values are nominal and subject to correction.

Standards

Referenced specifications

  • ASTM B-498
  • ASTM B-500
  • ASTM B-606
  • ASTM B-609
  • ASTM B-802
  • ASTM B-803
  • ASTM B-857 Shaped Wire Compact Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Supported (ACSS/TW)
  • ASTM B-957
  • ASTM B-958